Seleccione su país

Visite el sitio web global

FDH-1 Fieldbus Diagnostic HandheldFieldConnex® Fieldbus

Ventajas clave de un vistazo

  • Comprehensive diagnostics for the fieldbus physical layer
  • Handheld with display and integrated expert system
  • Fieldbus interface Ex ia, FISCO, Entity, and DART
  • For commissioning, online monitoring and troubleshooting
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Multi-language support
  • Operation in Zone 1/Class I, Div. 1
  • Choice of power options for different operating modes
  • PC software for enhanced interface and data backup

Mostrar más

Product Compliance: Europe – CE
Approval
FieldConnex® interface
FOUNDATION Fieldbus interface
PROFIBUS interface
Interface
Nota

Todos los documentos relacionados con los productos, como certificados, declaraciones de conformidad, etc., que se emitieron antes de la conversión con el nombre de Pepperl+Fuchs GmbH o Pepperl+Fuchs AG también se aplican a Pepperl+Fuchs SE.

EN
  • EN
  • DE

Datos técnicos de FDH-1

Fieldbus diagnostic handheld for comprehensive diagnostics of the fieldbus physical layer
Design / MountingHandheld/mobile
Installation in hazardous areaZone 1 / Div. 1
ConnectionFieldbus , Battery , 9V 6LR61 block, type alkaline, carbon-zinc, lithium iron disulfide, nickel-cadmium, nickel-metal hydride, or rechargeable lithium , USB
Fieldbus typeFOUNDATION Fieldbus/PROFIBUS PA
Rated voltageUN8.5 ... 35 V
Rated currentIN... 10 mA , if bus powered
DisplayLC display
KeypadMembrane 8 keys
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
LanguagesEnglish (default), German (optional), Portuguese (optional),
Ambient temperature-20 ... 50 °C (-4 ... 122 °F)
Storage temperature-20 ... 70 °C (-4 ... 158 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Connection typeFieldbus: Cable with test clips and cable with test plugs, 2.5 mm
Trigger output: Cable with 2 banana plugs
USB: Square type B socket
Degree of protectionIP44
Mass500 g
EU-type examination certificateZELM 14 ATEX 0531
MarkingEx-Hexagon II 2(1) G Ex ib [ia Ga] IIC T4 Gb ,
[exsign] II 3(1) G Ex ic [ia Ga] IIC T4 Gc ,
[exsign] II 3 G Ex ic IIC T4 Gc ,
[exsign] II (1) D [Ex ia IIIC Da] ,
[exsign] II (3) D [Ex ic IIIC Dc]
Bus
TypeFieldbus
Type of protectionia, ib
Internal capacitanceCi< 1.8 nF
Internal inductanceLi< 1.5 µH
Voltage Ui30 V
Bus
TypeFieldbus
Type of protectionic
Internal capacitance< 1.8 F
Internal inductance< 1.5 µH
Voltage Ui35 V
Outputs
TypeTrigger output
Maximum safe voltageUm140 V
Interface
TypeUSB interface
Maximum safe voltageUm253 V
Voltage Ui6 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012
CSA approvalCSA 16.70029275
Approved forClass I, Division 2, Groups A, B, C, D, T4
Associated equipment for Class I, Division 1, Groups A, B, C, D
Associated equipment for Class II, Division 1, Groups E, F, G
Associated equipment for Class III, Division 1
IECEx approvalIECEx ZLM 14.0012
Approved forEx ib [ia Ga] IIC T4 Gb ,
Ex ic [ia Ga] IIC T4 Gc ,
Ex ic IIC T4 Gc ,
[Ex ia IIIC Da] ,
[Ex ic IIIC Dc]
Scope of deliveryFDH-1 incl. carrying case, fieldbus connection cable, USB 2.0 cable, FDH-1 Manager software
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.