Seleccione su país

Visite el sitio web global

DP-LBF-I1.36.* Surge ProtectorFieldConnex® Fieldbus

Ventajas clave de un vistazo

  • Modular: protection module easy to replace
  • Intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus, or general-purpose
  • Protection module replaceable, interrupting or non-interrupting
  • Grounding of shield direct or via gas-discharge tube
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Compact and space-saving design
  • Installation on DIN rail in cabinet or field junction box

Mostrar más

Product Compliance: Europe – CE
Approval
FieldConnex® interface
FOUNDATION Fieldbus interface
PROFIBUS interface
Nota

Todos los documentos relacionados con los productos, como certificados, declaraciones de conformidad, etc., que se emitieron antes de la conversión con el nombre de Pepperl+Fuchs GmbH o Pepperl+Fuchs AG también se aplican a Pepperl+Fuchs SE.

EN
  • EN
  • DE

Datos técnicos de DP-LBF-I1.36.*

Surge protector, module for control cabinet installation (Ex ia)
Design / MountingCabinet installation
Installation in hazardous areaZone 1 / Div. 1
Rated voltageUr33 V
Rated currentIr500 mA
Voltage protection levelUp
Line/Linemax. 58 V category C1/C2
8/20 µsec
max. 50 V category C3 1 kV/µsec
max. 51 V category B2 10/700 µsec
max. 55 V category D1 10/350 µsec
Line/Earthmax. 1400 V category C1/C2
8/20 µsec
max. 1100 V category C1/C2
1 kV/µsec
max. 1000 V category B2 10/700 µsec
max. 1300 V category D1 10/350 µsec
Screen/Shield directly groundedmax. 25 V category C1/C2
8/20 µsec
max. 20 V category D1 10/350 µsec
Screen/Shield indirectly grounded (via GDT)max. 700 V category C1/C2
8/20 µsec
max. 600 V category C3 1 kV/µsec
max. 500 V category B2 10/700 µsec
max. 600 V category D1 10/350 µsec
Reaction timetA
Line/Linemax. 1 ns
Line/Earthmax. 100 ns
Screen/Shield-Earthmax. 100 ns
Overstressed fault modeaccording IEC 61643-21 line inoperable mode 3 lines 1 and 2 at 15,5kA (8/20µsec) lines 3 and 4 at 30kA (8/20µsec)
Series resistance in line1 Ω +/- 5 %
Impulse durability
Per line1 kA category D1 10/350 µsec ,
5 kA category C1/C2
8/20 µsec
Screen/Shield directly grounded5 kA category D1 10/350 µsec
Screen/Shield indirectly grounded (via GDT)4 kA category D1 10/350 µsec ,
10 kA category C1/C2
8/20 µsec
Capacitance
Line/Line800 pF
Line/Earth16 pF
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Climatic conditionsIEC 60721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Surge protectionIEC 61643-21
Ambient temperature-50 ... 80 °C (-58 ... 176 °F)
Storage temperature-50 ... 85 °C (-58 ... 185 °F)
Relative humidity≤ 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Connection typescrew terminals
Core cross sectionflexible wire 2.5 mm2 solid wire max. 4 mm2
Housing materialPolyamide PA 6.6
Degree of protectionIP20
MassProtection Module 20 g , base module 40 g
MountingDIN rail mounting
EU-type examination certificateKEMA 09 ATEX 0191 X
MarkingEx-Hexagon II 2(1)G Ex ia [ia Ga] IIC T6...T4 Gb
VoltageUi30 V
CurrentIi500 mA
Internal capacitanceCinegligible 0 nF
Internal inductanceLi negligible 0 µH
CertificateKEMA 09 ATEX 0190 X
MarkingEx-Hexagon II 3G Ex ic IIC T6...T4 Gc , [exsign] II 3G Ex nA IIC T6...T4 Gc
VoltageUi33 V
CurrentIi500 mA
Internal capacitanceCinegligible 0 nF
Directive conformity
Directive 2014/34/EUEN 60079-0:2018 , EN 60079-11:2012 , EN 60079-15:2015 + A1:2018

CSA approvalCSA 2437472
Control drawing116-0361
Approved forClass I, Zone 1, AEx/Ex ia IIC T4...T6,
Class I, Zone 2, AEx nC IIC T4...T6,
Class I, Zone 2, Ex nL IIC T4...T6,
Class I, Zone 2, AEx/Ex nA IIC T4...T6
Class I Div. 1, GP A, B, C, D T4...T6,
Class I Div. 2, GP A, B, C, D T4...T6,
Class I Div. 2, GP A, B, C, D T4...T6
IECEx approvalIECEx KEM 09.0088X
Approved forEx ia [ia Ga] IIC T6...T4 Gb ,
Ex ic IIC T6...T4 Gc , Ex nA IIC T4/T5/T6 Gc
Marine approvalpending
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.